Country / jurisdiction: Australia · Year: 2012 · Status: In force · Level: National · Type: Voluntary
As of December 2012 Chillers with capacities greater than 350kW sold in Australia must comply with the minimum energy
performance standards (MEPS) regulations.
Capacity: 350-499
Minimum COP
Air cooled 2.70
Water cooled 5.00
Minimum IPLV
Air cooled 3.70
Water cooled 5.50
Capacity: 500-699
Minimum COP
Air cooled 2.70
Water cooled 5.10
Minimum IPLV
Air cooled 3.70
Water cooled 6.00
Capacity: 700-999
Minimum COP
Air cooled 2.70
Water cooled 5.50
Minimum IPLV
Air cooled 4.10
Water cooled 6.20
Capacity: 1,000-1,499
Minimum COP
Air cooled 2.70
Water cooled 5.80
Minimum IPLV
Air cooled 4.10
Water cooled 6.50
Capacity: >1,500
Minimum COP
Air cooled 2.70
Water cooled 6.00
Minimum IPLV
Air cooled 4.10
Water cooled 6.50
Official source: https://www.energy.gov.au/sites/default/files/hvac-factsheet-chiller-efficiency.pdf