INTIEAUnited States · Wisconsin Uniform Residential Code (based on the 2009 IECC)PolicyIn force

Wisconsin Uniform Residential Code (based on the 2009 IECC)

Air leakage: Window and door assemblies: (a) General. Except as specified in par. (b), windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot, and swinging doors no more than 0.5 cfm per square foot, when tested…

Last changed 7 years ago.

Extracted view for reading · Original for compliance evidence

Lifecycle

  1. Effective
  2. Last change

Country / jurisdiction: United States · Year: 2016 · Status: In force · Level: State/Provincial · Type: Voluntary

Air leakage:

Window and door assemblies:

(a) General. Except as specified in par. (b), windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot, and swinging doors no more than 0.5 cfm per square foot, when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.

(b) Exception. Site-constructed doors and windows shall be sealed with gasketing or weatherstripping or shall be covered with a storm door or storm window.

Joint and penetration sealing:

(a) Exterior joints, seams or penetrations in the dwelling envelope, which are sources of air leakage, shall be sealed with durable caulking materials, closed with gasketing systems, taped, or covered with water-vapor-permeable house wrap.

Joints to be treated include all of the following:

1. Openings, cracks and joints between wall cavities and window or door frames.

2. Between separate wall assemblies or their sill-plates and foundations.

3. Between walls, roof, ceilings or attic ceiling seals, and between separate wall panel assemblies, including between interior and exterior walls.

4. Penetrations of utility services through walls, floor and roof assemblies, and penetrations through top and bottom wall plates.

(b) Sealing shall be provided at the attic and crawl space panels, at recessed lights and around all plumbing and electrical penetrations, where these openings are located in the dwelling thermal envelope.

(c) The sealing methods between dissimilar materials shall allow for differential expansion and contraction.

Recessed lighting. When installed in the dwelling envelope, recessed lighting fixtures shall be sealed to limit air leakage between conditioned and unconditioned spaces by one of the following means:

(a) The fixture shall be IC-rated and labeled with enclosures that are sealed or gasketed to prevent air leakage to the ceiling cavity or unconditioned space.

(b) The fixture shall be IC-rated and labeled as meeting ASTM E 283 when tested at 1.57 psi pressure differential with no more than 2.0 cfm of air movement from the conditioned space to the ceiling cavity.

(c)

1. The fixture shall be located inside an airtight sealed box with clearances of at least 0.5 inch from combustible material and 3 inches from insulation.

2. If the fixture is non-IC-rated, the box shall be constructed of noncombustible material that does not readily conduct heat.

Lighting Equipment. A minimum of 50 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps.

Specific insulation requirements:

(1) Ceilings with attic spaces.

(a) R-38 will satisfy the ceiling R-value requirement for a dwelling where the full height of uncompressed R-38 insulation extends over the wall top plate at the eaves.

(b) An attic-access cover shall be weatherstripped and insulated to a level equivalent to the insulation on the surrounding surfaces when the attic is an unconditioned space. A wood framed or equivalent baffle or retainer is required to be provided when loose fill insulation is installed, the purpose of which is to prevent loose fill insulation from spilling into the living space when the attic access is opened, and to provide a permanent means of maintaining the installed R-value of the loose fill insulation.

(2) Ceilings without attic spaces. Where the design of the roof or ceiling assembly does not allow sufficient space for the required R-49 insulation, the minimum required insulation for the roof or ceiling assembly shall be R-30. This reduction of insulation shall be limited to 500 square feet of ceiling area.

(3) Mass walls. The requirements of Table 322.31-1 are applicable to mass walls.

(4) Steel-frame ceilings, walls and floors.

(a) Steel-frame ceilings, walls and floors shall meet the insulation requirements of Table 322.32 or shall meet the U-factor requirements in Table

Official source: http://docs.legis.wisconsin.gov/code/admin_code/sps/safety_and_buildings_and_environment/320_325/322

Source

https://www.iea.org/policies/7145

Canonical document at the regulator. Always cite this URL — not the Vantage detail page — in compliance evidence.

Related in International

INTEnergy Newsoilprice:oilprice-article-45056NewsIn force

The U.S. Army Just Called China’s Bluff in the Rare Earth War

Just recently, in a span of about six weeks, one impressive company was selected by the U.S. Army to build and operate rare earth processing facilities on an American military base…the first time the Army has ever done this. That same company closed $100 million in institutional financing, giving it a war chest of roughly $130 million. It was also formally added to the Russell 3000 Index. And it locked in MOU’s for feedstock agreements covering billions of tonnes of rare earth-bearing material from sources across Wyoming, Appalachia…

14 hours ago
INTEnergy Newsoilprice:oilprice-article-45052NewsIn force

Oil Prices Ignore the Warning Signs in Physical Markets

Oil price movements since the start of March this year have become the topic of dozens of discussions. Many have been puzzled by futures prices and why they haven’t gone through the roof given the severe disruption in Middle Eastern supply. It appears the reason is sheer optimism and a bet on market adaptability. However, there is a problem with that. Adaptability has limits. Many commentators like to compare the current oil price—and supply—situation to 2022, when Russia’s incursion into eastern Ukraine prompted an actual…

15 hours ago
INTEnergy Newsoilprice:oilprice-article-45054NewsIn force

The World’s Largest Sand Battery Is Now Online

Modern power grids require a constant, real-time balance between supply and consumption. Unfortunately, the integration of wind and solar energy makes power grids unstable due to the intermittent nature of renewable energy generation. To prevent localized grid blackouts or harmful voltage spikes, utilities are increasingly pairing renewables with battery storage and/or rapid-response natural gas plants to smooth out fluctuating supply. However, Finland has now come up with a rather eccentric method to store excess renewable energy and release it…

16 hours ago
INTEnergy Newsrigzone:https://www.rigzone.com/news/wire/australia_to_study_first_new_oil_refinery_since_60s-28-jul-2026-184235-article/?rss=trueNewsIn force

Australia to Study First New Oil Refinery Since 60s

Prime Minister Anthony Albanese Tuesday announced a study for a new refinery in Karratha in Western Australia, backed by A$4 million ($2.8 million) of government funds.

17 hours ago
INTEnergy Newsoilprice:oilprice-article-45055NewsIn force

Refined Fuels, Not Crude, Are Driving the Oil Market Crunch

Oil prices have just come off a fresh two-month high as the crude oil market has tumbled this week amid signals of de-escalation in the U.S.-Iran conflict. Despite the slump in crude prices and the extreme volatility in the past five months, the refined product market continues to tighten with refining margins at record highs because the supply of petroleum products is much tighter than crude supply. Refining margins held at record highs even as crude oil prices soared last week to $100 per barrel. That’s because global gasoline, diesel,…

17 hours ago