Country / jurisdiction: Finland · Year: 2013 · Status: In force · Level: National · Type: Voluntary
Policy Requirement Level
Mandatory
Governance
Development Authority: Ministry of the Environment
Implementation Authority: Ministry of the Environment
Verification Authority: Ministry of the Environment
Enforcement Authority: Municipal building inspection
Prescriptive Compliance path
Energy Requirements:
Insulation
U-Values (W/m2.K)
Walls
Floor
Roof
Building elements of warm and cooled cold spaces
0.17
0.09
0.09
Building elements of semi-warm spaces
0.26
0.14
Windows
U-Values (W/m2.K)
Windows
Building elements of warm and cooled cold spaces
Building elements of semi-warm spaces
1.4
Total window area should not exceed 50% of total area of external walls
Air Leakage
4 m3/(h.m2) at 50 Pa