Country / jurisdiction: Chinese Taipei · Year: 2003 · Status: In force · Level: National · Type: Voluntary
This standard defines EER and COP of air cooled and water cooled chillers, starting from 2003 (first phase) and 2005 (second phase)
water cooled,volume compressor
CC <150RT
first phase: EER 3.50; COP4.07
second phase: EER 3.83; COP4.45
CC ? 150RT and ? 500RT
first phase: EER 3.60; COP 4.19
second phase: EER 4.21; COP 4.90
CC> 500
first phase: EER (kcal/h-W)4.00; COP 4.65
second phase: EER (kcal/h-W)4.73; COP 5.50
water cooled,centrifugal compressor
CC <150RT
first phase:EER (kcal/h-W)4.30; COP 5.00
second phase: CC EER (kcal/h-W)4.3 COP 5.00
CC ? 150RT and <300RT
first phase: EER (kcal/h-W)4.77; COP 5.55
Second phase: EER (kcal/h-W)4.77; COP 5.55
CC ? 300RT
first phase: EER (kcal/h-W)4.77; COP 5.55
second phase: EER (kcal/h-W)5.25; COP 6.10
air cooled:
first phase: EER 2.40; COP 2.79
second phase: EER 2.40; COP 2.79
Official source: https://www.moeaboe.gov.tw/ECW/populace/Law/Content.aspx?menu_id=1037