Country / jurisdiction: United States · Year: 2010 · Status: In force · Level: National · Type: Voluntary
Minimum Cooling Efficiency Standards for Double-Duct Air-Conditioning and Heating Equipment are defined as follow in code 10 CFR § 431.97 - Energy efficiency standards and their compliance dates.
This standard entered into force on January 1, 2010.
Small Double-Duct Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled) =65,000 Btu/h and <135,000 Btu/h
AC - Electric Resistance Heating or No Heating - EER = 11.2
AC - All Other Types of Heating - EER = 11.0
HP - Electric Resistance Heating or No Heating - EER = 11.0
HP - All Other Types of Heating - EER = 10.8
Large Commercial Double-Duct Packaged Air Conditioning and Heating Equipment (Air-Cooled) =135,000 Btu/h and <240,000 Btu/h
AC - Electric Resistance Heating or No Heating - EER = 11.0
AC - All Other Types of Heating - EER = 10.8
HP - Electric Resistance Heating or No Heating - EER = 10.6
HP - All Other Types of Heating - EER = 10.4
Very Large Double-Duct Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled) =240,000 Btu/h and <300,000 Btu/h
AC - Electric Resistance Heating or No Heating - EER = 10.0
AC - All Other Types of Heating - EER = 9.8
HP - Electric Resistance Heating or No Heating - EER = 9.5
HP - All Other Types of Heating - EER = 9.3